There are nine residential customersconnected to a distribution transformer of city subtation. Assume that the connected load is 29 kW per house and that the DF and diversity factor for the aroup of nine houses have been decided as 0.45 and 1.540, respectively. If the feeder has a system peak of 4500 kw/ phase and copper loss is 54 kw
/ph. Determine the total average loss power if the load factor is 0.53.